What is the DC breaking capacity for MCB of type iC60H ?

The MCB of type iC60H has DC breaking capacity as Follows:

- 1 pole: 10 KA - for Voltage up to 72 V DC.
- 2 poles: 10 KA for Voltage from 100 to 133 V DC
- 3 poles: 10 KA for Voltage from 100 to 133 V DC
- 4 Poles: 10 KA for voltage from 220 to 250 V DC.

attached data sheet for the MCB of type iC60H