For the Range of MCCB of type NS1600b to NS3200 - Can these CB be motorized or not ?

For the Range of MCCB from NS1600b to NS3200 (1600 A to 3200 A),
These Range must be:

1- Fixed (it can not be withdrawable).

2- Manually operated (it can not be motorized)

So in case the a CB in the above range is required motorized or withdrawable or both, you can refer to the air CB range (NT and NW) taking into consideration the differences in the dimensions (frame size) and the arc extinguish technique.