What are the possible ratings of ACB to use Micrologic trip units of type (Mic. 7.0) either (A or P or H) ?

The Micrologic trip unit of type Mic 7.0 (A or P or H) that is used for earth leakage protection with ACB can be used only up to 3200 A.

For the ratings starting from 4000 A up to 6300 A (4000 / 5000 / 6300 A), The earth leakage protection can be done using external Vigirex relay with Toroid or rectangular sensor.