For ATV61 & ATV71 ranges, What are the probable causes for "NLP fault" No Line power in case of the line power is connected?

If you have NLP fault while the line power is connected, it is most probably that Jumper between the terminals +24 & PWR is disconnected as attached below
i.e. The terminals +24 & PWR shoud be short-circuited