Does TAC I/NET support Interlock function ?

I/NET has three ways to do a mantrap:

  1. Event sequences and calculations -- limit to 5-7 SCUs per 7798C due to system loading
  2. Use a "standalone" third party device that is wired to the door and is not attached to I/ET at all
  3. Use the interlock wiring diagram that uses relay logic to function. This is also part of the I/NET System.

Note : A mantrap is a security device that monitors and controls two or more interlocking doors to a small room that separates a non-secured area from a secured area. These interlocking doors allow only one door to be open at any time.
 