How can I adjust the ATV312 to start the motor once the power is connected to it and the state of L1 is closed ?

In order to take the status of the Logic input into account to run or stop, you need to change the status of the parameter [2 wire type]  tCt in the I-O menu to be [Level] (LEL): instead of [Transition] (trn)

Note : Parameter can be accessed if [2/3 wire control] (tCC) = [2 wire] (2C)