In a (1 out of 3 ) source changeover system, is it ok to connect breakers with different ratings ?

It's ok to connect breakers with different ratings, as long as the below conditions are satisfied :

1. The breakers have to be of the same range ( NT or NW ).

2. The loads are distributed among the breakers according to each breaker's capacity.