Is it possible to display currents less than 20% of In in micro logic of Master pact NT and NW ?

Micrologic A control units measure the true (rms) value of currents.
They provide continuous current measurements from 0.2 to 20 In and with accuracy of 1.5 % In (including the sensors).
 
But if there is an external power supply (it ‘s an option ) it will be possible to display currents < 20 % In.
Below 0.05 In, measurements are not significant.

Between 0.05 and 0.2 In, accuracy is( 0.5 % In + 1.5 % In )