Technical FAQs

Ask a Question

What is the percentge of harmonic contect (percentage of non linear loads With respect to total loads) to use Standard duty Var plus Can LV capacitor ?

The standard duty Var plus can LV capacitor can be used with netoworks of harmonic content percentage <= 10 % from the total load of the network

above this percentage other solutions should be used as heavy duty capacitors or energy capacitors or even passive or active filters solution

(attached general specs for Standard duty Var plus can LV capacitors)
Was this helpful?
What can we do to improve the information ?