Is their a possible cascading between air circuit breaker as an upstream and molded case circuit breakers as a downstream ?

No it is not possible as The cascading is present only when you have two category A circuit breakers in upstream and in downstream.

Have in mind that just Masterpact NT and NW L1 are category A circuit breakers.

Kindly refer to Complementary Technical Information on the following link

http://www.global-download.schneider-electric.com/mainRepository/Index.nsf/DisplayProductDocumentation?OpenAgent&L=EN&App=Schneider&p=1887&c=42