Is the service breaking capacity (Ics) in acti 9 MCB ic60H is equal to the breaking capacity in DC and AC ?

According to IEC/EN 60947-2
For AC (Ph/N) 220-240 V for In (nominal rating current) 0.5 to 4 A at Icu=70 KA 
Ics= 100% Icu
 
For AC (ph/ph) 380-415 V for In (nominal rating current) 0.5 to 4 A at Icu=70 KA 
Ics= 100% Icu
 
For DC
For In 0.5 to 63 A and Icu =10 KA 
Ics= 100% Icu