Can we associate paralelle several VarplusCan HDUTY? For example: 3 x BLRCH200A240B40?

It is possible to connect in  parallel capacitors but in accordance with the instructions of connection, mainly capacitors do not connect directly to each other, but from each capacitor to the terminals of a contactor to limit the inrush current when switching a capacitor