What is the percentage for service short circuit (Ics) from the ultimate short circuit capacity (Icu) for NG125N CB ?

The service short circuit capacity  (Ics) from the ultimate short circuit capacity (Icu) for NG125N CB will differ according to the network (either AC or DC network) as follows:

- AC network: Ics = 75% Icu
- DC network Icu = 100 % Icu