How can we use Power meter to acquire the reading of KWH for 2 outgoings ?

We can do this configuration by using summation current transformer 2 inputs/ 1 output, by using the secondry of each CT ( first phase of load 1 and first phase of load 2 ) and to be connected to this summation current transformer, so we will use 3 current transformers for ( 3 phases ) + 3 summation current  transformer + power meter , in this way we could acquire the readings of KWH of the load 1+ load 2

For the selection of the summation transformer the load must be indentified .
Was this helpful?
What can we do to improve the information ?