Technical FAQs

Ask a Question

What is the maximum pluses per minute for the pluse inputs of Xenta 411 ?

The min pulse duration is 20ms, and this duration applies  to both high and low states. A complete min pulse cycle would be 20ms high + 20ms low (or vice versa) which equals 40ms. Therefore the max number of pulses per minute is (60/40)*1000 = 1500 pulse/min.

Was this helpful?
What can we do to improve the information ?