What is the expected breaking capacity of NSX breaker at 400HZ and 100V?

NSX is not designed for a frequency higher than 400Hz, there will be risk of excessive temperature rise and the accuracy of measurement cannot be guaranteed.
The breaking capacity of NSX on 110V voltage has never been done or tested before but according to the experts we can say that he values in the table for a 440V network can be used, normally the short circuit current on 400Hz is low.