How to control the speed of VFD through PLC and get a speed feedback ?

Please refer the attachment for the connection terminal details.

1. The analog input of 4-20mA from PLC to VFD should be connected between terminals AI2 & COM. The reference channel-1 should be programmed for AI2 and the parameter AI2 configuration should be programmed for 4 to 20mA.


2. The Analog output of 4 to 20mA from VFD to PLC should be connected between terminals AO1 & COM. The analog output assignment and scaling can be done through parameters as shown in the attachment.

 