For relay RXM4AB2B7 the max switching capacity for the contact is 1500VA for AC circuit so which means for 24VAC circuit I can pass 62.5Amps current through it ?

The relay contact capacity of 1500VA mentioned is the maximum capacity of relay contacts.

If the voltage reduces the capacity of the contacts also will reduce accordingly.

It is a 6Amps relay and the maximum operational current is 6Amps only.
 
It is not allowed to use the relay for 62.5 Amps, since the contacts are not capable to carry 62Amps.