Do we have instantaneous short time protection for (4 to 12)xIn for MCCB compact NSX

For frame size 100 for MCCB NSX we can use the micrologic 6.2 A to achieve the required range 4 to 12 x In as it provides instanteanous short time protection  range from 1.5 to 15 x In for the range of (40 to 160 A) and 1.5 to 12 x In for (250 to 400 A)  according to catalogue , you can check the attached PDF  ( highlighted Part) .