Does ATS48 soft starters alone (without breakers or protection components) withstands 50kA ?

The maximum prospective short-circuit current of the soft starters ref. ATS48 will depend on the supply voltage, coordination type, components used (breaker, contactor, etc) as well as the IEC standard IEC 60947-4-2

For example, ATS48C48Q for the same supply voltage 380 V:

·  Type 1 coordination: the max prospective short circuit current value is 70 kA.
·Type 2 coordination: the max prospective short circuit current value is 50 kA.

Please refer to the Attached document for the max prospective short circuit current value (ATS48-Coordination).

The ATS 48 does not protect from short circuit fault by itself (i.e. a breaker has to be installed for short circuit protection), Please refer to the protection functions provided by the ATS 48.