I have a 630A 4P 3d 100KA(380/415VAC) Plug in type NSX630S Micrologic 2.3 . When I connect it to the load ( Motor with 150A starting current ), it trips. What could be the problem?

Micrologic 2.3 is for Distribution application.
Micrologic 2.3M is for Motor application.
So you have to go for 2.3M.