Technical FAQs

Ask a Question

Please send me the X/R ratio of transformer for 1600kVA Trihal transformer?

The X/R ratio for the 1600kVA Trihal transformer can be calculated using the Trihal electrical characteristics (impedance & losses data) given normally in transformer datasheets
(attached )
values given in transformer datasheet:
-Load losses in Watts (at 75 C),
-No-load losses in Watts, and
-rated impedance voltage = Z%.

then calculation of the X/R ratio can be performed as follows:
we can obtain the R% as follows:
-R% = 100 x
[(Full load loss (W)-no load loss (W))/(transformer rated power (kVA)x1000)]

then using the impedance relation: Z = R+jX,
we can calculate X% = √(Z%² - R%²),
hence you can get X%/R% = X/R ratio.

Remarks:
1) Datasheets for both "standard losses" type and "reduced losses" type Trihal transformers are attached .
Also the impedance value shall be clear on transformer nameplate.

2) an example of above calculation has been attached for your reference.

Best regards.

 

Was this helpful?
What can we do to improve the information ?