I have a SM6 24KV distributed to 20 cells  What will be the heat dissipation ?

The amount of heat dissipated during operation is dependent on the SM6-24 function/cubicle type. 
 
In the attached technical schedule for SM6-24 you'll find enclosed the heat dissipated in watts for different functions, hence you can use this to estimate the total heat dissipated from the whole line-up by adding these values for different functions. 
 
Remark: in case you did not find the targeted cubicle type in attached schedule, please refer back to us .