How to rescale ION 8600 Energy meters from Kwh to Mwh ?

 To change the way the ION8600 scales voltage, current and power, adjust the PT or CT PRIMARY parameters as follows: 
For KW: 1000 < (CT*PT*3/1000) < 1,000,000, 
333 < (CT*PT) < 333,333 
For MW (CT*PT*3/1000) > 1,000,000 
(CT*PT) > 333,333 
NOTE: After scaling the PT PRIMARY, also scale the PT SECONDARY appropriately in order to keep the same ratio as the actual CT/PT. 
For example: 416:12 = 4160:120 = 4160000:120000
Was this helpful?