11KW Pump motor is at distance more than 300 meter away from the panel and it will be fed from VFD ATV61 type. What precautions to be considered?

If the motor cable length is more than 300 meters, it is recommended to use a sinus filter. The reference of sinus filter is VW3A5203 for the mentioned rati ng