For CL3 cubicle,is there an option for signalling contact draw-in / draw-out position 10NO-10NC contact?

The standard reference for draw-in/out CB truck position is 6NO+6NC contacts,if your application needs more contacts then one (or more) of the auxiliary contacts can be wired to an auxiliary relay in order replicate the indication. In this case wiring should be considering also that the indication out of the auxiliary relay will be dependent on the auxiliary voltage availability.
 