what are the precautions taken to protect the MCH connected to breakers?

The customer is advised to protect the control circuit using either a 10x38 2A fuse (for example P/N DF2CN02) or a 1P miniature circuit breaker of type iK60 or iC60 rated at 2A. Normally, any control circuit is advised to be protected by either one of the two above mentioned methods