If I will use IDMTL function to enhance the curves for the overload protection,will it isable the neutral protection (what if I will use the 4 pole breaker with the settings of 4p 4d, 4p 3d, 4p + N/

Kindly note the following when you use IDMTL function, the neutral protection is disabled and the dial setting on 4P breakers has no effect. Please refer the attached document. 