What will happen if the contactor of one of the steps of capacitor banks is not properly working for any malfunction reason,what will be the response of Varlogic?


In this case ,ERR3 will appear to notify of the error (Sequence not found: Step ratio does not match available step sequences).

According to the type of Varlogic, the action taken by it when a malfunction occurs by one of the contactors during normal operation will differ:
Varlogic NRC12 --> Varlogic display will indicate an alarm (ALARM 12, if enabled) and it will continue working as normal
Varlogic NR6/NR12 --> No alarm will appear on the Varlogic display and the regulator will continue working activating more steps if needed .
 