Is it feasible to have IP31 on SM6 cubicle?

SM6-24 units in switchboard provides IP3X and between compartments provides IP2X because SM6-24 units are designed for indoor applications, protection of the equipment inside the enclosure against harmful effects due to the ingress of water was never tested, accordingly it is not possible to upgrade the degree of protection to IPX1 with the standard offer. 
In order to make a special design for IPX1 protection, you need to check with MVS configuration/adaptation team lead by Mr.Nicolas Cador (we've attached information about team contacts) but first to fill-in the feasibility request form attached that will be evaluated by the team. 