Why Vijeo Citect shows #BAD variables while communicating to OTB1E0DM9LP over modnet Protocol?

Vijeo Citect monet driver has a default mechanism of block read by default.  Whereas OTB modules modbus address range for inputs is 0-99
and for output is 100-199 . Also OTB allocates modbus registers only when cards are used else they will remain reserved.  Due to this  behavior
of module when citect performs a default block read, communication fails with variables showing #BAD  on graphics page.

To over come this issue add "G" as a prefix to modbus addresses to force citect perfrom single read requests rather than block read.
For example using modbus address as G40100,  G40101 etc for variables in vijeo citect.