What is the suitable selection for for vigirex earth leakage module and toroid for NS breaker 800/1000A with sensitivityt 30mA ?


You can use the reference will be 56130  (Din Rail mounting ) and power supply 220-240 V AC  (type RH10M)

for the toroid we will use rectangular sensor with ie=1600A

kindly find the attached PDF for the vigirex module and toroids selection