Please confirm that in place of Mic 7.0 we can use ELR+ TOROID and it will work properly.

Kindly be informed that for earth leakage protection,you can use Vigirex and its toroid (MX shunt trip should be added to the breaker) instead of Micrologic 7 up to 3200A but, please consider the difference in sensitivity and time delay between both.

Please find attached the settings for both micrologic 7 and Vigirex RH99M.