Can we have auxiliary contacts in NSX breaker equipped with BSCM module

The BSCM module occupies the slots for 1OF and 1SDE and NSX cord occupies the slot of 1SD,as mentioned in the attached catalog pages,so it is possible to add 1OF for NSX100/250 and 3OF for NSX400/630,while there is no possibility to have a free contact SD or SDE with existence of BSCM module and NSX cord.