Technical FAQs

Ask a Question

Which trip unit in MCCB achieve LSI protection

1-For NSX MCCB :the required trip unit with adjustable Long time protection (L)and short time protection(S) with instantaneous protection (I) can be achieved with Micrologic 2 trip unit taking into consideration that the time delay for L and S functions is non-adjustable.

If these protection functions are required with adjustable time delay,thanks to offer the micrologic5 .

2-For NS MCCB:The required protection functions LSI can be achieved with Micrologic 5 with time delay adjustable for long time and short time protection functions
Was this helpful?
What can we do to improve the information ?