Can the CVS accommodate 6 wires of 95 Sq.mm in each pole to distribute power to the blocks ?

The maximum number of cables per phase is:
-For CVS 100/160/250 :2 cables 50 to 120 mm² using 2-cable Aluminum connector .
-For CVS 400/630 :2 cables 35 to 240 mm² using 2-cable Aluminum connector .