Is LTMR certified for Ex e type installation and can be installed in Zone 1 areas and please advice if it's approved by testing Authority such as BASEEFA or PTB.

LTMR is not certified for Ex e type installation .

The LTMR is certified for the Ex II (2) GD or Ex I (M2) and can be recommended for use with an Explosion proof Motor installed in Hazardous area.

The installation of the LTMR however , should be outside potentially explosive atmosphere.
If it required for the LTMR to be used in the potentially explosive atmosphere, than it should be installed inside an enclosure which is suitably rated to work in potentially explosive atmosphere.

We have the ATEX certificates as attached for this requirement from INERIS, There are no BASEEFA certificates available.