Technical FAQs

Ask a Question

Tripping time for reference LR9F5569

 Reference LR9F5569 is TeSys LRF - electronic thermal overload relay - 90...150 A - class 20
 Reference LR9F5569 comply with Standard IEC 60947-4 specifies a tripping time for 7.2 times the setting current In:
- class 20: between 6 and 20 seconds.
Datasheet link :
http://eshop.schneider-electric.com/product.aspx?productid=LR9F5569&dist=276&org=21&lang=EN