What is the Maximum Rating of TMD Trip units that can be installed with NSX 400/630 ?

Kindly be informed that the Trip unit of Type TMD are only used with NSX CCB up to 250 A only (frame 100/160/250) A and can not be used with NSX of frame sizes 400/630 A

Instead, you can use the trip units of Type Micro logic (where there are many options of Micro logic based on the supported protection functions), these trip unit is the one that is used with 400/630 A NSX