Technical FAQs

Ask a Question

What are the Closing conditions for the MN release coil inside NSX MCCB ?

If there is no supply to the MN release, it is impossible to close the circuit breaker,

either manually or electrically. Closing is ensured when the voltage supply to the

release U u 0.85 x Un. Below this threshold, closing is not guaranteed.

Was this helpful?
What can we do to improve the information ?