What is the maximum KVAR rating which can be installed in Prisma P?

Each cubicle can be equipped with up to 5 VarplusCan power factor correction Modules (100 kvar) or up to 4 VarplusCan with detuned reactor power factor correction Modules (50 kvar),
positioned one above the other.

 The cubicle has a ventilated roof that can be equipped with one or two fans.
 The door has cut-outs, one for the VarplusLogic power factor controller and another in the bottom for a filter.