Welcome to the Schneider Electric Website

Welcome to our website.

You can choose another country to view available products or go to our Global website for company information.

Choose another country or region

RM17UBE16 Product picture Schneider Electric

Range: Zelio Control

Electrical

RM17UBE16

RM17UBE16 Product picture Schneider Electric
Range: Zelio Control

Electrical

RM17UBE16

voltage control relay RM17-U - range 20..80 V AC

Show more characteristics >
Add to My Products Remove from My Products

  • Main
    range of product
    Zelio Control
    product or component type
    Modular measurement and control relays
    relay type
    Voltage control relay
    product specific application
    For single-phase and DC supply
    relay name
    RM17UBE
    relay monitored parameters
    Overvoltage and undervoltage detection
    Self-powered
    time delay
    Adjustable 0.1...10 s, 0 + 10 % on crossing the threshold
    switching capacity in VA
    1250 VA
    minimum switching current
    10 mA at 5 V DC
    maximum switching current
    5 A AC/DC
    power consumption in VA
    0...3.9 VA AC
    measurement range
    20...80 V voltage AC 50/60 Hz
    20...80 V voltage DC
    utilisation category
    AC-12 conforming to IEC 60947-5-1
    AC-13 conforming to IEC 60947-5-1
    AC-14 conforming to IEC 60947-5-1
    AC-15 conforming to IEC 60947-5-1
    DC-12 conforming to IEC 60947-5-1
    DC-13 conforming to IEC 60947-5-1
    DC-14 conforming to IEC 60947-5-1
    Complementary
    reset time
    1500 ms for time delay
    maximum switching voltage
    250 V AC/DC
    [Us] rated supply voltage
    24...48 V AC/DC, 50/60 Hz +/- 10 %
    supply voltage limits
    15...100 V AC/DC
    power consumption in W
    <= 1.6 W DC
    immunity to microbreaks
    20 ms
    control circuit frequency
    50...60 Hz +/- 10 %
    output contacts
    1 C/O
    nominal output current
    5 A
    measuring cycle
    <= 150 ms measurement cycle as true rms value
    hysteresis
    3 % fixed of threshold setting
    delay at power up
    <= 100 ms DC
    <= 500 ms AC
    measurement accuracy
    +/- 10 % of the full scale value
    repeat accuracy
    +/- 0.5 % for input and measurement circuit
    +/- 1 % for time delay
    measurement error
    < 1 % over the whole range with voltage variation
    0.2 %/°C with temperature variation
    polarity
    Non reversible polarity on DC supply
    quality labels
    CE
    overvoltage category
    III conforming to IEC 60664-1
    insulation resistance
    > 500 MOhm at 500 V DC conforming to IEC 60255-5
    > 500 MOhm at 500 V DC conforming to IEC 60664-1
    [Ui] rated insulation voltage
    250 V conforming to IEC 60664-1
    400 V conforming to IEC 60664-1
    operating position
    Any position without derating
    connections - terminals
    Screw terminals 1 x 0.5...1 x 4 mm² - AWG 20...AWG 11, solid cable without cable end
    Screw terminals 2 x 0.5...2 x 2.5 mm² - AWG 20...AWG 14, solid cable without cable end
    Screw terminals 2 x 0.2...2 x 1.5 mm² - AWG 24...AWG 16, flexible cable with cable end
    Screw terminals 1 x 0.2...2 x 2.5 mm² - AWG 24...AWG 12, flexible cable with cable end
    tightening torque
    0.6...1 N.m conforming to IEC 60947-1
    housing material
    Self-extinguishing plastic
    local signalling
    LED green for power ON
    LED yellow for relay ON
    mounting support
    35 mm symmetrical DIN rail conforming to EN/IEC 60715
    electrical durability
    100000 cycles
    mechanical durability
    <= 30000000 cycles
    operating rate
    <= 360 operations/hour under full load
    safety reliability data
    MTTFd = 502.2 years
    B10d = 470000
    width
    17.5 mm
    product weight
    0.08 kg
    Environment
    electromagnetic compatibility
    Emission standard for industrial environments conforming to EN/IEC 61000-6-4
    Emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3
    Immunity for industrial environments conforming to NF EN/IEC 61000-6-2
    standards
    EN/IEC 60255-6
    product certifications
    CSA
    C-Tick
    GL
    GOST
    UL
    directives
    89/336/EEC - electromagnetic compatibility
    73/23/EEC - low voltage directive
    ambient air temperature for storage
    -40...70 °C
    ambient air temperature for operation
    -20...50 °C
    relative humidity
    95 % at 55 °C conforming to IEC 60068-2-30
    vibration resistance
    0.35 mm (f = 5...57.6 Hz) conforming to IEC 60068-2-6
    1 gn (f = 57.6...150 Hz) conforming to IEC 60255-21-1
    shock resistance
    5 gn conforming to IEC 60068-2-27
    IP degree of protection
    IP20 (terminals) conforming to IEC 60529
    IP30 (casing) conforming to IEC 60529
    pollution degree
    3 conforming to IEC 60664-1
    dielectric test voltage
    2 kV AC 50 Hz, 1 min conforming to IEC 60255-5
    2 kV AC 50 Hz, 1 min conforming to IEC 60664-1
    non-dissipating shock wave
    4 kV conforming to IEC 60255-5
    4 kV conforming to IEC 60664-1
    4 kV conforming to IEC 61000-4-5
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    REACh
    Product environmental profile
    Product end of life instructions
    Available
    Contractual warranty
    Warranty period
    18 months
  • Documents & Downloads

    Language
    • English
    Catalogue
    Date
    Size
    Add to My Documents
    Date 1/9/18
    Size 8.4 MB
    Certificate
    Date
    Size
    Add to My Documents
    Date 9/21/18
    Size 5.8 MB
    Date 8/6/18
    Size 1 MB
    UL Listed RM17, RM22, RM35, RM8487
    Date 8/2/18
    Size 213 B
    End of life manual
    Date
    Size
    Add to My Documents
    Date 12/14/17
    Size 92.5 KB
  • Technical FAQs

    No results found
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Single-Phase and DC Voltage Control Relays
    Dimensions and Mounting



  • Connections and Schema

    Single-Phase and DC Voltage Control Relays
    Wiring Diagram



    Application Scheme


    (1)
    To sensitive loads


  • Technical Description

    Function Diagram
    Control of Overvoltage and Undervoltage in Window Mode


    Legend

    Tt Time delay after crossing of threshold

    Un Nominal supply voltage

    U Monitored supply voltage

    H Hysteresis

    U> Overvoltage threshold

    U< Undervoltage threshold

    11-12, 11-14 Output relay connections

    Relay status: black color = energized.