Welcome to the Schneider Electric Website

Welcome to our website.

You can choose another country to view available products or go to our Global website for company information.

Choose another country or region

RM35TF30 Product picture Schneider Electric

Range: Zelio Control

Electrical

RM35TF30

RM35TF30 Product picture Schneider Electric
Range: Zelio Control

Electrical

RM35TF30

multifunction phase control relay RM35-T - range 194..528 V AC

Show more characteristics >
Add to My Products Remove from My Products

  • Main
    range of product
    Zelio Control
    product or component type
    Modular measurement and control relays
    relay type
    Multifunction control relay
    product specific application
    For 3-phase supply
    relay name
    RM35TF
    relay monitored parameters
    Asymmetry
    Phase failure detection
    Phase sequence
    Undervoltage and overvoltage in window mode
    time delay
    Adjustable 0.1...10 s, +/- 10 % of the full scale value
    switching capacity in VA
    1250 VA
    measurement range
    208...480 V voltage AC
    Complementary
    reset time
    <= 1500 ms for at 480 V
    maximum switching voltage
    250 V AC
    250 V DC
    minimum switching current
    10 mA at 5 V DC
    maximum switching current
    5 A AC
    5 A DC
    supply voltage limits
    194...528 V AC, 3 phases
    control circuit voltage limits
    - 12 % + 10 % Un
    power consumption in VA
    0...22 VA at 400 V AC 50 Hz
    voltage detection threshold
    < 194 V
    control circuit frequency
    50...60 Hz +/- 10 %
    output contacts
    2 C/O
    nominal output current
    5 A
    measurement voltage limits
    176...528 V AC
    hysteresis
    2 %
    delay at power up
    <= 650 ms
    measuring cycle
    <= 140 ms measurement cycle as true rms value
    threshold adjustment voltage
    +2...+10 % in the range 480 V AC
    +2...+20 % in the range 220...440 V AC
    -12...-2 % in the range 220 V AC
    2...20 % of Un selected
    -20...-2 % in the range 380...480 V AC
    voltage range
    220...480 V phase to phase
    adjustment of asymmetry threshold
    5...15 % of Un selected
    repeat accuracy
    0.3 % for time delay
    0.5 % for input and measurement circuit
    measurement error
    < 1 % over the whole range with voltage variation
    0.05 %/°C with temperature variation
    response time
    < 200 ms in the event of a fault
    marking
    CE
    overvoltage category
    III conforming to IEC 60664-1
    insulation resistance
    > 500 MOhm at 500 V DC conforming to IEC 60255-5
    > 500 MOhm at 500 V DC conforming to IEC 60664-1
    [Ui] rated insulation voltage
    400 V conforming to IEC 60664-1
    supply frequency
    50/60 Hz +/- 10 %
    operating position
    Any position without
    connections - terminals
    Screw terminals 1 x 0.5...1 x 4 mm² - AWG 20...AWG 11, solid cable without cable end
    Screw terminals 2 x 0.5...2 x 2.5 mm² - AWG 20...AWG 14, solid cable without cable end
    Screw terminals 1 x 0.2...1 x 2.5 mm² - AWG 24...AWG 12, flexible cable with cable end
    Screw terminals 2 x 0.2...2 x 1.5 mm² - AWG 24...AWG 16, flexible cable with cable end
    tightening torque
    0.6...1 N.m conforming to IEC 60947-1
    housing material
    Self-extinguishing plastic
    local signalling
    LED green for power ON
    LED yellow for relay ON
    LED yellow for fault
    mounting support
    35 mm symmetrical DIN rail conforming to EN/IEC 60715
    electrical durability
    100000 cycles
    mechanical durability
    <= 30000000 cycles
    operating rate
    <= 360 operations/hour under full load
    utilisation category
    AC-12 conforming to IEC 60947-5-1
    AC-13 conforming to IEC 60947-5-1
    AC-14 conforming to IEC 60947-5-1
    AC-15 conforming to IEC 60947-5-1
    DC-12 conforming to IEC 60947-5-1
    DC-13 conforming to IEC 60947-5-1
    safety reliability data
    MTTFd = 399.5 years
    B10d = 360000
    width
    35 mm
    product weight
    0.13 kg
    Environment
    electromagnetic compatibility
    Emission standard for industrial environments conforming to EN/IEC 61000-6-4
    Emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3
    Immunity for industrial environments conforming to EN/IEC 61000-6-2
    standards
    EN/IEC 60255-1
    product certifications
    CSA
    C-Tick
    GL
    GOST
    UL
    directives
    89/336/EEC - electromagnetic compatibility
    73/23/EEC - low voltage directive
    ambient air temperature for storage
    -40...70 °C
    ambient air temperature for operation
    -20...50 °C
    relative humidity
    95 % at 55 °C conforming to IEC 60068-2-30
    vibration resistance
    0.35 mm (f = 5...57.6 Hz) conforming to IEC 60068-2-6
    1 gn (f = 57.6...150 Hz) conforming to IEC 60255-21-1
    shock resistance
    15 gn for 11 ms conforming to IEC 60255-21-1
    IP degree of protection
    IP20 (terminals) conforming to IEC 60529
    IP30 (casing) conforming to IEC 60529
    pollution degree
    3 conforming to IEC 60664-1
    dielectric test voltage
    2 kV 1 min AC 50 Hz
    non-dissipating shock wave
    4 kV
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    REACh
    Product environmental profile
    Product end of life instructions
    Contractual warranty
    Warranty period
    18 months
  • Documents & Downloads

    Language
    • English
    Catalogue
    Date
    Size
    Add to My Documents
    Date 1/9/18
    Size 8.4 MB
    Certificate
    Date
    Size
    Add to My Documents
    Date 6/25/18
    Size 5.8 MB
    Date 8/6/18
    Size 1 MB
    UL Listed RM17, RM22, RM35, RM8487
    Date 8/2/18
    Size 213 B
    Instruction sheet
    Date
    Size
    Add to My Documents
    End of life manual
    Date
    Size
    Add to My Documents
    Product environmental
    Date
    Size
    Add to My Documents
  • Technical FAQs

    No results found
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Multifunction 3-Phase Supply Control Relays
    Dimensions and Mounting



  • Connections and Schema

    Multifunction 3-Phase Supply Control Relays
    Wiring Diagram



  • Technical Description

    Function Diagrams
    Phase Sequence Control, Phase Failure Detection (U measured < 0.7 x nominal supply voltage) and Asymmetry Detection


    Control of Overvoltage and Undervoltage in Window Mode


    Legend

    A Asymmetry thershold

    Tt Time delay after crossing of threshold

    H Hysteresis

    U> Overvoltage threshold

    U< Undervoltage threshold

    L1, L2, L3 Phases of the supply voltage monitored

    R Output relay

    Relay status: black color = energized.